How to choose an automatic transfer switch for mains-to-generator changeover

Summary

To choose an automatic transfer switch, establish the supply arrangement, maximum switched current, voltage, pole configuration, load duty, fault level and control requirements. Then match those requirements to a documented model. Charter Controls lists Radin RDS5 four-pole, three-position ATS units from 25 A to 630 A for 400/415 V AC systems. Automatic changeover involves an interruption; it should not be described as uninterrupted power.

Explore the Radin RDS5 range or discuss your application with Charter Controls.

A practical guide for UK panel builders, featuring Radin RDS5 automatic transfer switches

A standby generator needs a suitable switching arrangement to supply the intended loads when mains power fails. For a panel builder, selecting the automatic transfer switch means considering the whole application: the supplies, the loads, the protection and the operating sequence.

This guide explains the checks to make before ordering and shows how the Radin RDS5 products listed by Charter Controls fit into that selection process.

What is an automatic transfer switch and how does it work?

An automatic transfer switch, or ATS, combines source-changeover equipment with controls that respond to the condition of the power supplies. A manual changeover switch requires an operator to initiate the transfer; an ATS manages the agreed sequence automatically.

In a typical mains-to-generator application, mains power normally supplies the load. If the monitored supply becomes unacceptable, the controller can request a compatible generator to start. Once the standby supply meets the configured conditions, the switch transfers the load. When mains power returns and remains acceptable for the configured delay, the system can transfer back and release the generator-start request according to its settings.

The generator controller, sensing functions and transfer settings must work together. Electric start alone does not establish compatibility with an ATS.

What information do you need before choosing an ATS?

Establish the supply and load requirements

Record the voltage, frequency and phase arrangement of both sources, together with the maximum current that will pass through the switch in each intended operating condition. If the generator supplies only selected loads, define that backed-up section clearly.

Generator kVA is useful background information, but it does not establish the required ATS rating by itself. Consider the current carried during normal mains operation as well as standby operation.

Check the pole arrangement and neutral design

The neutral and earthing arrangement determines whether the neutral needs to be switched. A three-phase supply does not, by itself, settle the choice between three-pole and four-pole equipment. The RDS5 products in the table below are four-pole models; their suitability still depends on the installation design.

Match the switching duty to the loads

List the equipment being supplied, including motors, pumps, compressors, transformers and electronic loads. Check the utilisation category at the relevant voltage and current. For example, the AC-33 categories address motor or mixed-load switching duties. Confirm the precise category and rating for the selected unit rather than applying a headline range claim to every model.

Check fault ratings and protection coordination

The ATS must be suitable for the prospective fault level and the specified protective devices. Radin describes the RDS5 as a Class PC transfer switch. Class PC equipment is not intended to interrupt short-circuit current, so the design must include the appropriate coordinated protection.

Supply monitoring and transfer control do not replace overload or short-circuit protection. Ask for the selected model’s fault ratings and the protective-device combinations supporting those ratings.

Check the enclosure and connections

Allow for the actual switch dimensions, cable sizes, bending space, terminal access, heat dissipation and installation clearances. The listed models use top supply inputs and a bottom load output. Check ambient conditions and any applicable derating before settling the current rating or enclosure layout.

IEC 60947-6-1 is the relevant transfer-switching equipment standard. Request the manufacturer’s declaration and supporting documentation for the exact model, including the edition referenced. A newer edition of a standard does not establish that an existing product has been assessed to it.

Does automatic changeover mean uninterrupted power?

No. In an open-transition arrangement, the switch disconnects one source before connecting the other. This is known as break-before-make switching. A standby generator also needs time to start and establish an acceptable supply after mains failure.

The total interruption therefore includes more than the switching mechanism’s transfer time. It depends on source-failure detection, configured delays, generator start-up and supply acceptance as well as the changeover itself.

If a PLC, communications device or other load cannot tolerate that interruption, assess an appropriate UPS or other engineered continuity arrangement. Also decide how machinery should stop, retain its state and restart after a transfer.

BS 8519:2020: why does a life-safety ATS need a bypass?

Life-safety and fire-fighting applications need additional consideration. BS 8519:2020, Selection and installation of fire-resistant power and control cable systems for life safety, fire-fighting and other critical applications. Code of practice, includes recommendations for the electrical supply arrangements serving these systems.

Where continued occupation of a building depends on the availability of its life-safety and fire-fighting equipment, the code recommends a single or dual bypass arrangement so the changeover device can be maintained without taking the critical plant out of service.

A manual maintenance bypass provides a separate electrical path around the ATS. With suitable isolation, this allows the ATS to be taken out of circuit for maintenance or replacement while the load remains supplied. It also provides a route around a failed ATS, subject to the available supply and the designed operating procedure. A manual operating handle on the ATS is different: it still operates the same switching mechanism and does not bypass a failed device.

The bypass must therefore be electrically separate from the ATS switching path. This does not necessarily mean a separate enclosure: complete ATS assemblies are available with bypass and isolation equipment housed together. The important distinction is between the ATS device and the complete bypass-equipped assembly.

Where does the Radin RDS5 fit?

Radin describes the RDS5 as a Class PC transfer switch with a built-in controller, conformity to IEC 60947-6-1 and utilisation categories up to AC-33A. These are relevant characteristics when assessing equipment for a BS 8519:2020 application. The RDS5 is the automatic transfer component; the required manual bypass and isolation arrangement must be specified separately as part of the system design.

The absence of an integral bypass does not, by itself, exclude the RDS5 from an application requiring BS 8519:2020. It can be considered as the ATS within a suitably designed bypass-equipped system, subject to confirmation of the exact model’s ratings, controller and supporting documentation. Compliance depends on the complete assembly and installation, including the bypass, isolation, protection and fire-safety design.

Which ATS control functions matter inside a panel?

The listed Radin RDS5 models combine four-pole, three-position switching with RS485 Modbus communications, a generator-start output and fire-link input. Assess each function against the required operating sequence.

  • Monitoring and delays: establish the required source-acceptance conditions, transfer delay, return delay and generator start and stop sequence. Confirm the selected controller’s available settings.
  • Generator interface: check the start-signal requirements against the generator controller and its installation instructions.
  • Three switching positions: Source I, OFF and Source II provide a defined centre OFF state. They do not remove the need for a complete safe-isolation procedure.
  • Communications: check the Modbus register information, settings and required BMS or SCADA integration.
  • Fire-link input: confirm the exact input logic, commanded action and reset behaviour. The presence of an input does not establish that the complete system meets a fire-safety specification.
  • Remote display: consider where operators need to view status and adjust authorised settings.

Charter Controls lists the optional RD-LCD02 remote LCD programmer with a 2 m cable for RDS5 status display and parameter access. Include the accessory in the panel specification if door-mounted access is required.

Which Radin RDS5 automatic transfer switch should you consider?

The following individual products are listed by Charter Controls. They are described as four-pole, three-position units for 400/415 V AC, 50 Hz systems, with top supply inputs and bottom load output. Use the linked stock code to open the corresponding product page.

The number within a model family code is not necessarily the selected unit’s rated current. For example, RDS5-125-4PIII-BZ63A is listed as a 63 A product. Use the full stock code and the product’s rated-current field when ordering. Stock-code punctuation above follows the individual listings.

This table identifies products for further assessment. It does not establish suitability from current rating alone. Confirm the exact controller specification, duty, fault ratings, protective devices, dimensions, price and availability before ordering.

Worked example choosing a starting point for a pump control panel

Illustrative example, not a completed installation design. A panel builder is specifying a 400/415 V, three-phase backed-up section of a pump control panel. The project brief states a maximum switched current of 100 A, with mains and a compatible standby generator. The design calls for a switched neutral, automatic changeover, remote status monitoring and a door-mounted display.

The RDS5-125-4PIIIBZ100A is a sensible product to investigate because its listing gives 100 A, four poles, three positions, RS485 Modbus and a generator-start output. The RD-LCD02 is the associated display accessory to review.

The selection remains provisional. The designer still needs to check motor duty and restart behaviour, environmental derating, fault level, coordinated protection, generator compatibility, controller settings and installation space. If any check requires a different rating or arrangement, revise the selection. Do not assume that simply moving to a higher current rating resolves every issue.

What should you send Charter Controls for selection support?

Send the details you already have, together with a single-line diagram where available:

  • Both source voltages, frequency and phase arrangement.
  • Maximum switched current and the loads requiring standby power.
  • Motor, transformer and other significant load details.
  • Generator make, model, controller and start-interface requirements.
  • Neutral and earthing arrangement, fault level and protective-device details.
  • Required operating sequence, delays, communications and remote display.
  • Any BS 8519:2020 or life-safety specification, including the proposed manual bypass and isolation arrangement.
  • Enclosure conditions, available space, cable arrangement, quantity and required delivery date.

If part of the specification is still being developed, identify it in the enquiry so it can be discussed before a product is selected.

Explore Radin automatic transfer switches, or send Charter Controls your application details for help selecting a suitable model.

View automatic transfer switches | Contact Charter Controls | Call 01424 850660.

Frequently asked questions

What does an automatic transfer switch do?

An automatic transfer switch monitors the relevant supplies and controls changeover between them. In a compatible mains-to-generator system, the control sequence can request generator start, wait for an acceptable standby supply and transfer the connected load.

What size automatic transfer switch do I need?

Choose the rated current for the maximum intended current through the switch in each operating condition. Also check voltage, load duty, environmental derating, fault ratings and protection coordination. Generator kVA alone is not enough to select an ATS.

Do I need a three-pole or four-pole ATS?

The neutral and earthing design determines whether the neutral must be switched. The Radin RDS5 products listed in this guide are four-pole devices. Have the complete supply arrangement checked before selecting the pole configuration.

What is a three-position transfer switch?

A three-position transfer switch has Source I, OFF and Source II positions. The centre OFF position disconnects the load from both sources through the switching mechanism. Safe maintenance still requires the appropriate isolation, lock-off and proving-dead procedure.

Does an ATS provide uninterrupted power?

An open-transition ATS briefly disconnects the load while changing sources. Following mains failure, a standby generator also needs time to start and establish an acceptable supply. Loads requiring continuous power may need a suitably engineered UPS arrangement.

Can a Radin RDS5 ATS start a generator?

The listed models include a generator-start output. Automatic starting depends on a compatible generator controller and correctly designed wiring and settings. Check the generator interface before ordering.

Can I monitor a Radin RDS5 remotely?

The listed models include RS485 Modbus communications. Charter Controls also lists the optional RD-LCD02 remote LCD programmer with a 2 m cable. Confirm controller compatibility, communications settings and the required monitoring functions for the project.

Does BS 8519:2020 require a bypass built into the ATS?

The recommendation concerns a bypass arrangement for the installation. It provides a separate supply path so the ATS can be isolated for maintenance while critical plant remains supplied. Bypass equipment can share an enclosure with the ATS, but a manual operating handle on the ATS is not a maintenance bypass.

Where can I buy Radin automatic transfer switches in the UK?

Charter Controls lists Radin RDS5 automatic transfer switches from 25 A to 630 A on charter-controls.com. Check the individual product page or contact the team to confirm the specification, price and availability for your chosen model.