EYC DPT02-D Digital Universal Input Signal Converter – Analogue Output + RS-485 + Relay

DIN-rail signal converter with isolated output, RS-485 Modbus RTU and relay alarm for mA/V/RTD/TC/resistance inputs, 85-253 V AC supply, 3-digit LED display.

Stock Code: DPT02-D

Minimum Quantity:

ex VAT (%) VAT n/a
From ex VAT (%) VAT n/a Call Free
Discount:
Price ex VAT (%):
VAT n/a:
Due In Due In
Notify when back in stock
Product not available

EYC DPT02-D Digital Universal Input Signal Converter is a DIN-rail signal converter designed to scale and isolate field signals for PLC, SCADA and instrumentation systems. It accepts multiple input types (mA, V, RTD, thermocouple and resistance) and converts them to standard outputs. This -D version provides one analogue output, RS-485 Modbus RTU and a relay alarm output.

🔧 Technical Highlights:

  • Universal inputs: DC voltage (0-10 V, 2-10 V, 0-1 V, 0-5 V, 0.2-1 V, 1-5 V); DC current (0-20 mA, 4-20 mA); RTD (Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000; 2/3/4-wire); thermocouple (B, E, J, K, N, R, S, T, U; internal cold junction compensation); linear resistance (0-10 kΩ); potentiometer (10-100 kΩ).
  • Analogue output ranges: current (0-20 mA, 4-20 mA, 20-0 mA, 20-4 mA) and voltage (0-1 V, 0.2-1 V, 0-5 V, 1-5 V, 0-10 V, 2-10 V, 1-0 V, 1-0.2 V, 5-0 V, 5-1 V, 10-0 V, 10-2 V).
  • Outputs: 1 analogue output (A.OUT1) on terminals 11 (-) and 12 (+); RS-485 on terminals 13 (D-) and 14 (D+); relay contacts on terminals 21 (COM), 22 (NO) and 23 (NC).
  • Relay alarm: configurable HI/LO alarm direction with hysteresis (display value or 0-100%) and ON/OFF delay 0-3600 s; relay rating up to 6 A, 277 V AC / 30 V DC (1500 VA / 180 W).
  • RS-485 communication: Modbus RTU (master or slave), baud rates 9600 to 115200 bps.
  • Display & setup: 3-digit LED display (-199 to +999), 0-2 decimal places, keypad programming; sampling 4 cycles/sec; response time adjustment 0.5-60 sec.
  • Analogue output performance: 16-bit resolution; load resistance for current output < 500 Ω; voltage output load ≥ 10 kΩ; signal error detection supported.
  • Power & auxiliary supply: 85-253 V AC supply; auxiliary output 16-25 V DC, 23 mA for 2-wire/3-wire transmitters.
  • Isolation: galvanic isolation between power supply, analogue input, analogue output and RS-485.
  • Power connections: 85-253 V AC on terminals 31 and 34.
  • Input & excitation terminals (1-4): 1 = +TC / Pt(b) (RTD 3/4-wire); 2 = -mA / -V / -TC / Pt(B) (RTD 2/3/4-wire) / Potm.1 / Lin.R; 3 = +mA / Pt(A) (RTD 2/3/4-wire) / Potm.3 / Lin.R; 4 = +exc. / +V / Pt(a) (RTD 4-wire) / Potm.2. Typical wiring: mA input on 2(-) & 3(+); V input on 2(-) & 4(+); thermocouple on 1(+) & 2(-); potentiometer on 2/4/3; auxiliary transmitter supply on 4(+V) & 2(-V).
  • Environment & build: operating -10 to +60 °C, 0-95% RH (non-cond.); IP20; ABS UL94V-0; 99.5 x 25.5 x 104.2 mm; approx. 158 g.
  • Calibration: 20-point linear calibration function.

✅ Benefits:

  • Converts many sensor and transmitter signals to standard analogue outputs to simplify panel design
  • Built-in galvanic isolation helps prevent ground loops and improves measurement stability
  • Local LED display and keypad make scaling and diagnostics quicker during commissioning
  • DIN-rail form factor saves space in control panels
  • 20-point linear calibration supports fine tuning for demanding processes

🚀 Applications:

  • Factory automation signal conditioning
  • Energy, water circulation and process skids
  • Oil & gas and marine instrumentation panels
  • Metal, cement, pulp & paper and chemical plants
  • Food & beverage and pharmaceutical process control

Designed for stable, isolated signal conversion, DPT02 helps deliver reliable measurements and control signals in industrial automation environments.

FAQs

  • Q: How is the relay output wired on DPT02-D?
    A: Use terminal 21 for relay COM, terminal 22 for NO and terminal 23 for NC. Relay behaviour (HI/LO alarm, hysteresis and delay) is configurable from the keypad.
  • Q: How do I connect the analogue output and RS-485?
    A: Wire A.OUT1 to terminals 11 (-) and 12 (+). Wire RS-485 D- to terminal 13 and D+ to terminal 14 for Modbus RTU communication.
Supply Voltage110Vac, 230Vac
Output Relay / Channels0-20mA, 4-20mA, 20-0mA, 20-4mA, 0-1V, 0.2-1V, 0-5V, 1-5V, 0-10V, 2-10V, 1-0V, 1-0.2V, 5-0V, 5-1V, 10-0V, 10-2V, SPCO
MountingDIN Rail
Size25.5mm
Inputs0-10V, 2-10V, 0-1V, 0-5V, 0.2-1V, 1-5V, 0-20mA, 4-20mA, PT10, PT20, PT50, PT100, PT200, PT250, PT300, PT400, PT500, PT1000, 2/3/4w, B, E, J, K, N, R, S, T, U, 0-10K Ω, 10-100 Ω
ProtectionIP20
Type File Name
Data Sheet EYC_DPT02-en-20170201.pdf
Instruction Manual DPT02_manual-20170418.pdf