GIC liquid level controller for monitoring electrically conductive liquids in tanks. Suitable for filling and draining control using electrode probes, with DIN rail mounting and a 1 C/O relay output.
Key features
- Selectable filling or draining operation
- Dual level monitoring
- Adjustable sensitivity for conductive liquids
- Green power and red relay status LEDs
- 24-240V AC/DC supply
Technical specifications
| Supply voltage | 24-240V AC/DC (-15%/+10%) |
|---|
| Supply frequency | 50/60Hz +/-10% |
|---|
| Output | 1 C/O relay, 8A at 250V AC (resistive) |
|---|
| Monitoring | Dual level |
|---|
| Sensitivity | 5-100 kohm |
|---|
| Adjustable delay | Not available |
|---|
| Operating temperature | -20 to +60 degrees C |
|---|
| Mounting | DIN rail |
|---|
| Probe supply | 12 Vp-p, less than 1 mA |
|---|
Application notes: For electrically conductive liquids only. Not suitable for pure water, oils, corrosive liquids or flammable liquids. For single-level operation, the manufacturer does not recommend direct pump control; see the datasheet for details. Probes are listed separately in the manufacturer datasheet.